2. Unlocking/Locking Base Console
Press F1 to unlock base console. The default password
is 0800.
See Installation/Owner’s Manual to customize password.
To enter password, press F3 (Next) to move the cursor
one digit to the right.
Use the arrow keys to change the numeric value to 0800,
then press to enter.
The base console is now unlocked.
After completion of steps 3 - 5, press F1 to lock the base
console, if desired.
The base console locks automatically if no keys are
pressed within 30 minutes.
3. Setting Date and Time
To set time and date format: The defaults are
24-hour clock (military time) and mm/dd/yyyy format.
To change to 12-hour clock or dd/mm/yyyy format if
desired, go to MAIN MENU, select System, ; select
Configuration, ; select Date Format or Time
Format, ; then select the preferred configuration.
Press F3 (OK) to set.
To set time and date: go to MAIN MENU, select
System, ; select Set Date or Set Time, ;
follow menu prompts and use PREV and NEXT soft keys
to select the desired values. Press F3 (OK) to set.
4. Adding Sensors
Press MENU key, use arrow keys to select Sensors and press .
Select Add New Sensor, .
Follow procedure 4a if adding a hardwired sensor and procedure 4b if adding a wireless sensor.
4.a Adding Wired Sensors
Select Wired, . Select the type of sensor being
connected. You can opt to select from a list of Common
names or create a Custom name (16 characters or less).
After assigning a name, continue to follow the on-screen
prompts to complete the programming of your sensor.
See Installation/Owner’s Manual for details. Repeat setup
for each additional hardwired sensor. The steps vary
depending on the sensor type being added. Note: For
detailed information on configuring a 4-20mA sensor,
please refer to the Installation/Owner’s Manual.
4.b Adding Wireless Sensors
Remove cover from wireless sensors until setup is complete. With the wireless sensor unmounted
and located near the base console, apply power to the sensor using remote power supply or 2 AA
batteries before starting setup. It is recommended that power is applied to one sensor at a time,
and that the setup is completed for that sensor before adding subsequent wireless sensors.
Select Wireless, press . The base console searches for a connection with the wireless sensor.
This may take 1-2 minutes.
Note: Press the Reset Button on the sensor to restart the search
process if necessary. Verify
that the number shown
on the base console screen
matches the number on the
sensor’s PC board. Press .
If the list of number(s) on
the screen does not contain the number found on the sensor’s PC board, press F1 (Cancel) to
continue the search process. Select the output relay to which the wireless sensor is to be assigned,
then press . Continue the setup based upon the type of wireless sensor being added.
Wireless Multi-Function Sensor (EA-WMFS)
Wireless multi-function sensors provide a wireless transmitter for connection to a wired sensor.
Select the type of sensor to be connected to the wireless multi-function sensor, then press .
Assign a Common name or Custom name to the sensor, and continue to follow on-screen
prompts to complete the setup.
Note: Custom names are limited to 16 characters for all sensors.
Note: The Wireless Multi-Function Sensor (EA-WMFS) supports the following sensor types:
Blue Temperature Probe (TEMP-L-W and TEMP-L-S)
Red Temperature Probe (TEMP-H-W and TEMP-H-S)
White Temperature Probe (TEMP-UL-S)
Supervised WaterBug® Sensor (W-S-S and W-UC-S)
Contact Sensors (N.O. and N.C.)
Note: Not for use with the HA-III+ or 4-20mA sensors. These sensors can only be configured as
wired.
Wireless Temperature Sensor (EA-WTS)
Assign a Common name or Custom name to the sensor, and continue to follow on-screen
prompts to complete the setup.
Note: Custom names are limited to 16 characters for all sensors.
Wireless Humidity Sensor (EA-WHS)
Assign a Common name or Custom name to the sensor, and continue to follow on-screen
prompts to complete the setup.
Note: Custom names are limited to 16 characters for all sensors.
Repeat setup for each additional wireless sensor. The steps will vary depending on the type of
sensor being added.
Verifying Signal Strength
After temporarily mounting the wireless sensors in the
desired location, verify the signal strength at the base
console by pressing MENU , select Sensors, ;
select Performance, ; then select the sensor to
be checked, . It may take as long as 30 seconds to
acquire the current signal strength.
If No Data is displayed in place of bars, it indicates that
recent signal strength information has not been received.
If this persists for 1-2 minutes without displaying any
performance bars, it is a strong indication that your
sensor is placed out of range with the base console.
If fewer than two bars are shown, it is recommended that
the sensor be relocated to obtain a better signal. Refer to
the instruction sheet included with the wireless sensor for
details on ensuring optimum signal strength.
5. Advanced Settings
Refer to the Installation/Owner’s Manual found online at www.winland.com for configuring the
following advanced EA800 settings:
• Configuring the Relays
• Pausing Monitoring and Cancelling Pause
• Replacing a Sensor
• Editing Sensor Parameters
• Changing Sensor Data Collection Frequency
• Changing the Buzzer Setting
• Clearing the Alarm/Sensor Logs
• Saving/Loading Configuration Settings
• Exporting the Stored Logs
Sensor Model Number
Example: EA-WTS = Wireless Temperature Sensor
Reset Button